There are many different type of electrical bus system schemes available
but selection of a particular scheme depends upon the system voltage, position
of substation in electrical power system, flexibility needed in system and cost
to be expensed.
The main criteria’s to be considered
during selection of one particular Bus – Bar Arrangement Scheme among others
(i) Simplicity of system
(ii) Easy maintenance of different equipment.
(iii) Minimizing the outage during maintenance.
(iv) Future provision of extension with growth of demand
(v) Optimizing the selection of bus bar arrangement scheme so that it gives maximum return from the system.
(ii) Easy maintenance of different equipment.
(iii) Minimizing the outage during maintenance.
(iv) Future provision of extension with growth of demand
(v) Optimizing the selection of bus bar arrangement scheme so that it gives maximum return from the system.
Some very commonly used bus bar arrangement are discussed below
Single Bus System
Single Bus System is simplest and cheapest one. In this scheme all the
feeders and transformer bay are connected to only one single bus as shown.
Advantages of single bus system
This is very simple in design
This is very cost effective scheme
This is very convenient to operate
This is very cost effective scheme
This is very convenient to operate
Disadvantages of single bus system
One but major difficulty of these type of arrangement is that,
maintenance of equipment of any bay cannot be possible without interrupting the
feeder or transformer connected to that bay.
The indoor 11KV switchboards have quite often single bus bar
arrangement.
Single Bus System with Bus
Sectionalizer
Some advantages are realized if a single bus bar is sectionalized with
circuit breaker. If there are more than one incoming and the incoming sources
and outgoing feeders are evenly distributed on the sections as shown in the
figure, interruption of system can be reduced to a good extent.
Advantages of single bus system with
bus sectionalizer
If any of the sources is out of system, still all loads can be fed by
switching on the sectional circuit breaker or bus coupler breaker.
If one section of the bus bar system is under maintenance, part load of the substation can be fed by energizing the other section of bus bar.
If one section of the bus bar system is under maintenance, part load of the substation can be fed by energizing the other section of bus bar.
Disadvantages of single bus system
with bus sectionalizer
As in the case of single bus system, maintenance of equipment of any bay
cannot be possible without interrupting the feeder or transformer connected to
that bay.
The use of isolator for bus sectionalizing does not fulfill the purpose. The isolators have to be operated ‘off circuit’ and which is not possible without total interruption of bus – bar. So investment for bus-coupler breaker is required.
The use of isolator for bus sectionalizing does not fulfill the purpose. The isolators have to be operated ‘off circuit’ and which is not possible without total interruption of bus – bar. So investment for bus-coupler breaker is required.
Double Bus System
In double bus bar system two identical bus bars are used in such a way
that any outgoing or incoming feeder can be taken from any of the bus.
Actually every feeder is connected to both of the buses in parallel
through individual isolator as shown in the figure.

By closing any of the isolators one can put the feeder to associated bus. Both of the buses are energized and total feeders are divided into two groups, one group is fed from one bus and other from other bus. But any feeder at any time can be transferred from one bus to other. There is one bus coupler breaker which should be kept close during bus transfer operation. For transfer operation, one should first close the bus coupler circuit breaker then close the isolator associated with the bus to where the feeder would be transferred and then open the isolator associated with the bus from where feeder is transferred. Lastly after this transfer operation he or she should open the bus coupler breaker.

By closing any of the isolators one can put the feeder to associated bus. Both of the buses are energized and total feeders are divided into two groups, one group is fed from one bus and other from other bus. But any feeder at any time can be transferred from one bus to other. There is one bus coupler breaker which should be kept close during bus transfer operation. For transfer operation, one should first close the bus coupler circuit breaker then close the isolator associated with the bus to where the feeder would be transferred and then open the isolator associated with the bus from where feeder is transferred. Lastly after this transfer operation he or she should open the bus coupler breaker.
Advantages of Double Bus System
Double Bus Bar Arrangement increases the flexibility of system.
Disadvantages of Double Bus System
The arrangement does not permit breaker maintenance with out
interruption.
Double Breaker Bus System

In double breaker bus bar system two identical bus bars are used in such
a way that any outgoing or incoming feeder can be taken from any of the bus
similar to double bus bar system. Only difference is that here every feeder is
connected to both of the buses in parallel through individual breaker instead
only isolator as shown in the figure. By closing any of the breakers and its
associated isolators, one can put the feeder to respective bus. Both of the
buses are energized and total feeders are divided into two groups, one group is
fed from one bus and other from other bus similar to previous case. But any
feeder at any time can be transferred from one bus to other. There is no need
of bus coupler as because the operation is done by breakers instead of
isolator. For transfer operation, one should first close the isolators and then
the breaker associated with the bus to where the feeder would be transferred
and then he or she opens the breaker and then isolators associated with the bus
from where feeder is transferred.
One and a half Breaker Bus System

This is an improvement on the double breaker scheme to effect saving in
the number of circuit breakers. For every two circuits only one spare breaker
is provided. The protection is however complicated since it must associate the
central breaker with the feeder whose own breaker is taken out for maintenance.
For the reasons given under double breaker scheme and because of the
prohibitory costs of equipment even this scheme is not much popular. As shown
in the figure that it is a simple design, two feeders are fed from two
different buses through their associated breakers and these two feeders are
coupled by a third breaker which is called tie breaker. Normally all the three
breakers are closed and power is fed to both the circuits from two buses which
are operated in parallel. The tie breaker acts as coupler for the two feeder
circuits.
During failure of any feeder breaker, the power is fed through the
breaker of the second feeder and tie breaker, therefore each feeder breaker has
to be rated to feed both the feeders, coupled by tie breaker.
Advantages of One and a half Breaker
Bus System
During any fault on any one of the buses, that faulty bus will be
cleared instantly without interrupting any feeders in the system since all
feeders will continue to feed from other healthy bus.
Disadvantages of One and a half
Breaker Bus System
This scheme is much expensive due to investment for third breaker.
Main and Transfer Bus System

This is an alternative of double bus system. The main conception of Main
and Transfer Bus System is, here every feeder line is directly connected
through an isolator to a second bus called transfer bus. The said isolator in
between transfer bus and feeder line is generally called bypass isolator. The
main bus is as usual connected to each feeder through a bay consists of circuit
breaker and associated isolators at both side of the breaker. There is one bus coupler
bay which couples transfer bus and main bus through a circuit breaker and
associated isolators at both sides of the breaker. If necessary the transfer
bus can be energized by main bus power by closing the transfer bus coupler
isolators and then breaker. Then the power in transfer bus can directly be fed
to the feeder line by closing the bypass isolator. If the main circuit breaker
associated with feeder is switched off or isolated from system, the feeder can
still be fed in this way by transferring it to transfer bus.
Switching operation for transferring
a feeder to transfer bus from main bus without interruption of power
(i) First close the isolators at both side of the bus coupler breaker.
(ii) Then close the bypass isolator of the feeder which is to be
transferred to transfer bus.
(iii) Now energized the transfer bus by closing the bus coupler circuit
breaker from remote.
(iv) After bus coupler breaker is closed, now the power from main bus
flows to the feeder line through its main breaker as well as bus coupler
breaker via transfer bus.
(v) Now if main breaker of the feeder is switched off, total power flow
will instantaneously shift to the bus coupler breaker and hence this breaker
will serve the purpose of protection for the feeder.
(vi) At last the operating personnel open the isolators at both sides of
the main circuit breaker to make it isolated from rest of the live system.
So it can be concluded that in Main & Transfer Bus System the
maintenance of circuit breaker is possible without any interruption of power.
Because of this advantage the scheme is very popular for 33KV and 132 KV
system.
Double Bus System with Bypass
Isolators

This is combination of the double bus system and main and transfer bus
system. In Double Bus System with Bypass Isolators either bus can act as main
bus and second bus as transfer bus. It permits breaker maintenance without
interruption of power which is not possible in double bus system but it
provides all the advantages of double bus system. It however requires one
additional isolator (bypass isolator) for each feeder circuit and introduces
slight complication in system layout. Still this scheme is best for optimum
economy of system and it is best optimum choice for 220KV system.
Ring Bus System

The schematic diagram of the system is given in the figure. It provides
a double feed to each feeder circuit, opening one breaker under maintenance or
otherwise does not affect supply to any feeder. But this system has two major
disadvantages. One as it is closed circuit system it is next to impossible to
extend in future and hence it is unsuitable for developing system. Secondly,
during maintenance or any other reason if any one of the circuit breaker in
ring loop is switch of reliability of system becomes very poor as because
closed loop becomes opened. Since, at that moment for any tripping of any
breaker in the open loop causes interruption in all the feeders between tripped
breaker and open end of the loop.