There are no of protections for Alternator. in that Negative phase sequence Relay is one. A brief information about Negative phase sequence Relay .
Negative Phase sequence Relay (46):-
Purpose:- protection Against UN BALANCING LOAD
Causes for unbalancing :-
Ø Asymmetries'(un transposed lines)
Ø Un balanced loads on Alternator
Ø Asymmetric faults & Open Ckt
Effect on Alternator by Negative Phase Sequence Currents:-
Ø it's induces double frequency currents in the surface of rotor, Retaining rings & Slot wedges
Ø A small degree in the field winding.
Negative Phase Sequence is Phenomena generally found in motors,
the formula for positive phase sequence is : Ip= Ir + a * Iy + a^2*Ib
the formula for negative phase sequence is : In= Ir + a ^2* Iy + a*Ib
As the name suggest the sequence of current or the mmf(magnetic flux) is in reverse order, a reverse order current in stator will produce a reverse order mmf, now this reverse order mmf is rotating in direction opposite to the rotor of the motor, So the stator mmf to rotate at twice the System frequency & induces Eddy currents in to the rotor .
This Eddy current in your rotor leads to overheating and finally burning of winding.
Due to these reasons High & Possibility dangerous temp. on rotor winding in a short time.
Technical Requirements:-
Ø Time lag over current relay with negative sequence filter
Type of Relays:-
Ø Electro mechanical relay (induction disc type) time over current with Extremely inverse characteristics.
Ø Static relays with time over currents characteristics which matches I^2 *t capability curves for generator.
Note:- This relay always compare the three phases currents.
Inputs for relay:- Phase protection CT's(CT Core Class 3P,5P..)